HO5V-K,HO7V-K

100% Spark Tested | 99.97 % Cu Purity | 101% Conductivity

CABLE STRUCTURE

Conductor

Fine Stranded Copper (Class 5 - Flexible Plain Copper) to

VDE 0295 IEC 60228

Insulation PVC insulation compound TI-1
Colour

Green/Yellow, Blue, Black, Brown, Grey, Orange,

Pink, Red, Violet, White, Green, Yellow or other colours

Flame propagation Flame retardant test as per IEC 60332-1

TECHNICAL DATA

Operating Temp -20°C to max.+80°C
Nominal voltage HO5V-K : 300/500 V
HO7V-K : 450/750 V
Test voltage HO5V-K : 2000 V
HO7V-K : 2500 V
Insulation resistance Min. 10 MΩ x km
Min. bending radius 4 x cable diameter

HO5V-K (300/500 V )

Size in mm2 Nos/dia. (Nom. ) Insulation Thickness Outer Dia Max C.R in
    in mm (nom.) in mm (Appx.) ohm/km Copper
0.5 16/0.200 0.60 2.10 39.00
0.75 24/0.200 0.60 2.20 26.00
1 32/0.200 0.60 2.70 19.50
  • All are class 2 solid conductor
  • Insulation grade is TI1

Note:

The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IEC 60228 /DIN VDE 0295 / IS 8130 / BS 6360 or UL83

HO7V-K (450/750 V)

Size in mm2 Nos/dia. (Nom. ) Insulation Thickness in mm (nom). Outer Dia in mm (Appx) Max C.R in ohm/km Copper 
1.5 30/2.50 0.70 3.25 13.30
2.5 50/0.250 0.80 3.80 7.98
4 56/0.300 0.80 4.50 4.95
6 84/0.300 0.80 5.25 3.30
10 140/0.300 1.00 6.50 1.91
16 224/0.300 1.00 8.00 1.21
25 350/0.300 1.20 10.10 0.78
35 490/0.300 1.20 11.30 0.554
50 703/0.300 1.40 13.50 0.386
70 988/0.300 1.40 15.30 0.272
95 1349/0.300 1.60 18.00 0.206
120 608/0.500 1.60 19.80 0.161
150 760/0.500 1.80 22.30 0.129
185 943/0.500 2.00 23.90 0.106
240 1225/0.500 2.20 26.80 0.0801
  • All are class 5 stranded conductor
  • Insulation grade is TI1

Note:

The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance of IEC 60228 /DIN VDE 0295 / IS 8130 / BS 6360 or UL83

Download Catalogue