CONDUCTOR
Thin strands of electrolytic copper are multi-drawn for uniformity of resistance, dimension and flexibility. The drawn strands are uni-laid with high precision and compacted. Thus forming a perfectly circular conductor which enables reduction in overall diameter for space saving in high density wiring.
INSULATION
Specially formulated 105 Degrees heat resistant & flame retardant PVC insulation is used. The HR FR property retards the propagation of flame without compromising safety
MARKING
The cables are printed with generic marking "AXELON MAGNUM EQUILAY"
COLOURS
Red, Yellow, Blue, Green, Black, Yellow/green, Grey, White. Other Colors available on Request.
PACKING
Packing 90 meters / 180 meters / 270 meters / 100 yards
SIZE, DIMENSIONS & RATINGS
SINGLE CORE UNSHEATHED CABLES IN VOLTAGE GRADE 1.1 KV AS PER IS: 694
Nominal Cross Sectional Area of Conductor |
Number / Nom. Dia of Wires (Nom.) |
Thickness of Insulation (Nom.) |
Overall Diameter Max. |
Current Capacity #2 Cables Single Phase AC or DC
|
D.C.Resistance (Max.) at 20°c |
|||
---|---|---|---|---|---|---|---|---|
Sq. mm | Number / mm | mm | mm | Amps | Amps | Ohm / km | ||
1.00 | 19/0.260* | 0.70 | 2.70 | 14.00 | 15.00 | 18.10 | ||
1.50 | 19/0.320* | 0.80 | 3.10 | 17.00 | 19.00 | 12.10 | ||
2.50 | 37/0.290* | 0.80 | 3.70 | 22.00 | 26.00 | 7.41 | ||
4.00 | 37/0.370* | 0.90 | 4.30 | 30.00 | 34.00 | 4.60 |
# As per IS 3961 (PART V) - 1968. The number & diameter of conductor strands are for reference only and governed by conductor resistance.
The above data is indicative only and may be revised without prior information. Axelon will not be responsible for any damages arising out of incorrenct application of its proudct.
* As per conductor class 2 of IS:8130/1984
© Copyright Axelon Cables. All Rights Reserved.
Develop By : Design 2 Develop India